    • No.:
    • Brand :
    • Weight:

    Protection system diagram:The main advantages1. Satisfy the stability requirement - less than one cycle of tripping time (average 0.75 cycles per week)2. Highly efficient alternative high impedance sc

    1. Detailed information

    Protection system diagram:

    20141121084460736073.jpg

    The main advantages

    1. Satisfy the stability requirement - less than one cycle of tripping time (average 0.75 cycles per week)

    2. Highly efficient alternative high impedance scheme

    3. Improved safety through dual-principle (differential and direction) and CT saturation detection

    4. High reliability - first - class patent solution, only 2ms unsaturated current can be made

    judgment

    5. Maintain simplified and cost-saving - modular structure, general hardware, and reduce spare parts inventory, plug and play module

    6. Use high speed communication to reduce wiring and installation cost - the interaction between relay and relay is realized through the exchange of input and output between relays

    7. Efficient and flexible information access - multiple communication and protocol options

    8. Reduce installation space requirements through a compact design - multifunctional device integrated protection and control features, programmable buttons and LED and communication interfaces

    9. Application flexibility - multi-i/O selection, programmable logic (FlexLogicTM), modularization, user protection and control functions

    10. Reduce system accident analysis time and analysis cost - event sequence report, record wave, data record, IRIG-B time synchronization

    11. Circuit breaker monitoring - monitoring circuit breaker condition by analog quantity I/O, large range of measurements, circuit breaker arc current and tripping counter

    12. Embedded IEC 61850 statute - no external specification converter

    To use:

    1. Simple bus application, with up to 6 feeder lines, with circuit breaker failure protection function

    2. High voltage and ultra-high voltage substation integrated bus protection and measurement

    3. Advanced bus copy scheme

    4. Independent use can also be used as a component of automation substation control system

    Features:

    Protection and control

    Fast tripping, anti-ct saturation and CT fault detection

    Braking and instantaneous differential protection

    Phase, neutral and grounding instantaneous and time-delay protection

    Voltage, neutral and auxiliary overvoltage protection

    Dynamic bus profiling

    Breaker failure protection

    External section check

    Pass -

    Network selection - Ethernet optical fiber (redundant selection), RS422, RS485,

    G. 703, C37.94

    Various regulations -IEC 61850, UCA 2.0, DNP 3.0, Modbus, IEC 60870-5-104, Ethernet global data (EGD)

    Binary data exchange between direct I/O-UR relays

    Monitoring and measurement

    Tripping loop monitoring

    Measurement - current, voltage and frequency

    Record wave - up to 64 record record

    Event record - records 1024 events with time labels, 0.5ms digital input scan

    User programmable failure report

    User interface and programming

    The front panel screen and keyboard are used for local direct access, and RS232 is used for on-site PC access

    The user can program the local display, LED and button.

    Using FlexLogicTM, FlexCurvesTM and FlexElementsTM to implement user protection and control functions.

    Equipped with EnerVista LaunchPad software - simplified relay setup and programming.

    Supports multiple languages - French, Chinese, Russian.

    Protection and control

    B30 busbar differential protection system is a kind of applicable to single busbar scheme of busbar protection system, the protection system can be configured for six most circuits, it can provide high security, low impedance busbar protection, movement time less than a cycle. B30 can also be used for typical high impedance schemes. Using B30 does not require special or assisted CT, so the total cost of the system can be reduced.

    Other advanced features of B30 include circuit breaker failure protection, CT fault monitoring, under-voltage monitoring and dynamic bus profiling. Because of its unique flexibility (the maximum allowable level of CT variation in the terminal is 32:1), B30 is the ideal solution for different bus differential protection schemes. To enhance the security in important protection applications, B30 can be equipped with optional redundant dual power.

    Bus protection

    B30 can be used to protect the basic configuration system of single bus for up to 6 loops. B30 bus protection system is an exquisite design of busbar protection relay. Compared with traditional bus protection relay, B30 is smaller. The modular structure of B30 enables its functional configuration to increase and decrease according to the application requirements, so B30 can meet the requirements of various applications. For example, using multiple B30 can provide protection for larger busbar systems, in which each B30 is responsible for the protection of a segment of the bus, with up to six inputs.

    B30 has braking and no braking (instantaneous) differential protection to make it more secure. The principle of differential and current direction is used to protect the brake bus. In order to ensure the stability of busbar protection and the speed of the bus protection during the occurrence of the break-through fault, the maximum of the input current of the braking current is given. The principle of current direction is to detect the relationship between the current and the current. B30 can achieve an average of less than one cycle per week (0.75 cycles).

    CT saturation detection

    This element is used to detect CT saturation during external failure, so it does not trigger internal failure. This element does not require additional security to move quickly during internal failure. The CT saturation detection element is realized by analyzing the track of differential current and brake current. This patent scheme requires only 2ms unsaturated current to be judged.

    CT failure detection

    This feature monitors the size of the differential current. When the current maintains an integral value within a preset time range, the function emits a CT alarm.

    External section inspection

    The external section check is an optional feature that prevents the false action of the bus during CT failure. If a current input of B30 is idle, then a set of current signals can be introduced from the independent CT to the idle current input. These currents can be synthesized from the outside and then connected to the B30 relay. Two phase flow components can be used to check the above independent differential current values, thus realizing the monitoring of the main differential protection function.

    Dynamic bus profiling

    B30 can complete dynamic copying. The built-in programmable logic is used to remove the need for auxiliary relays, and the built-in programmable logic can also dynamically include current or removal of current in the differential zone. This allows the B30 protection configuration to be consistent with the actual bus configuration without the external switching of the CT loop. Because of the need to use a secondary relay (for current switching), the cost savings are realized and the reliability of the system is increased. The monitoring auxiliary switch function and contact difference alarm function of B30 increase its security.

    Backup protection

    B30 provides backup protection, such as under-voltage monitoring and phase delay overcurrent protection. B30 is also used as a gateway for SCADA systems to provide input channels for backup simulation and/or high impedance traditional products in the existing system.

    Breaker failure protection

    Circuit breaker failure protection function can be confirmed by a indicates the circuit breaker tripping within the prescribed period of time was not clear whether the fault, if after confirm the fault still is not clear, then, must implement the tripping protection again. B30 can be equipped with 6 independent circuit breaker failure protection functions. Start and block circuit breaker failure protection function through input contact or external communication. B30 can be used to perform fully independent circuit breaker protection for circuit breakers associated with bus systems.

    Monitoring and measurement

    B30 has a comprehensive record, measurement and monitoring capabilities. The use of these functions can replace dedicated fault - record and event sequence records.

    The measurement of the voltage and current of each loop is high and high

    The standard features of the protective device. The current parameter as the total waveform

    The value of the effective value or the value of the effective value and the phase Angle value of the working frequency (phase).

    Diagnostic functions such as record wave, event record and data recording combined with EnerVista software can greatly reduce troubleshooting time and simplify the generation of system failure reports.

    Wave record

    Up to 64 recorded channels can be configured to monitor any physical I/O points or internal Numbers and simulation variables. Waveform tracking and digital state function provide visual display of the bus system and the operation data captured during a particular trigger event. The sampling rate can reach up to 64 sampling/weekly waves, and 64 failure records can be stored in the relay.

    Event record

    The most recent 1024 events were captured with 0.5ms of digital input scan time to provide the SOE record function. Use the EnerVista software tools can be integrated from multiple devices of the event log, and use the IRIG - B time synchronization characteristics of the whole system of UR relay event records of time synchronization in order to achieve more accurate fault analysis and more efficient troubleshooting.

    User interface and programming

    The B30 front panel provides powerful local HMI functionality. The local display screen is used for monitoring, status information display, fault diagnosis and controller configuration. When the user-defined conditions are met, the display displays user-configurable information (the combination of text information and activated data). The use of a small keyboard is easy to access, and a small keyboard can be used to modify the set value of the relay.

    The front panel is equipped with 48 user programmable leds. These leds can be used to display important status information. The role of the LED is the external indicator light, so the use of the LED is not necessary to use the external indicator light. In addition, the B90 is equipped with 14 pre-programmed LED and user-based LED labels.

    The front panel also provides a RS232 interface for in-place PC access, which can be used in conjunction with EnerVista Launchpad software to facilitate quick and easy access to the relay. If you use an Ethernet interface, you can access the relay more easily through the network.

    User programmable button

    User programmable buttons can be used to perform manual control, operating circuit breaker or blocking function. The external switch and dual position relay can be replaced by the mechanical locking output controlled by the programmable button. There are 7 programmable control buttons (3 standard configurations, 4 optional configurations) and 12 larger user programmable buttons (optional configuration) with B30 supply. The control function of each button can be realized by programming, and the button operation can be recorded directly in the order of events. This record plays an auxiliary role in troubleshooting. Buttons can be tagged and their functions are clearly visible.

    A variety of languages

    B30 supports multiple languages. The local display, front panel, EnerVista setup software and the product manual are all available in French, Chinese and Russian. It is easy to switch between English and user selection in the local display screen.

    FlexLogicTM, FlexElementsTM, FlexCurvesTM

    B30 is equipped with powerful configuration and programming tools, including:

    FlexLogicTM: simplifies the use of programming and B30, and implements powerful and flexible protection and control solutions.

    FlexElementsTM: user can define protection and control functions.

    FlexCurvesTM: defines additional user curvilinear forms.

     

    Multi-set value setting group


    The non-volatile memory of B30 stores six sets of independent set value setting groups. B30 is equipped with an easy-to-use and fully programmable mechanism responsible for instant switching enabled Settings. Multiple set setting groups apply to all protection elements.


    communication

    B30 supports a variety of communication media and protocols compatible with new and existing communications equipment and facilities.


    Network options include optical fiber Ethernet (optional redundant configuration) and RS485 interface. With the advent of high-speed LAN network for relay communication, remote I/O information on LAN can be used to carry out internal control of the relay, which will save a lot of internal control wiring.


    The B30 supported regulations include IEC61850, DNP 3.0, Modbus RTU, Modbus TCP/IP and iec 60870-5104. The use of these protocols makes the connection between B30 and the substation automation system easy and easy, and these specifications are integrated within the B90 without external specification transformation devices.


    Interoperability with the built-in IEC 61850 specification


    IEC 61850 is a new international standard for information exchange and interoperability between intelligent devices in substations. Using B30 compliant with IEC 61850 standard, the protection and control of substation can be reduced cost and simplified engineering design, debugging and maintenance process. During the seven years of implementation of UCA2.0, GE has been leading the way, and now GE is taking the lead in adopting the iec 61850 standard.


    The iec 61850 standard adopts the seamless connection of multi-vendor IED devices. In addition to the interoperability of the devices, these regulations are also designed to control substations through the LAN rather than through the scattered wiring of the RTU. The distributed control of several ieds is implemented in the point-to-point communication mode of the Ethernet network, and this control mode does not require the connection of RTU to the remote SCADA master station. High-speed information transfer saves a lot of expensive hard wire connections.


    Direct I/O communication


    This feature enables a number of UR ieds to exchange binary data through dedicated optical fibers (single or multimode), RS422, G703, or C37.94. Since ieds are directly connected with a ring or redundant (double) ring in this scheme, no switching equipment is needed.


    EnerVistaTM

    EnerVistaTM is an industry-leading software program that simplifies aspects of the B90 application. It becomes a multi-purpose tool for monitoring the bus status in real time and viewing any amount of electrical value measured by B90. EnerVistaTM software is equipped with powerful COMTRADE tools and event sequence viewers that have the ability to analyze any cause of failure. EnerVistaTM software is supplied with B90.


    EnerVistaTMLaunchPad


    The EnerVistaTM LaunchPad is a powerful software package that provides users with all the Settings and support tools needed to configure and maintain all GE Multilin products. The package also includes a file system that ensures that all manuals, application records and other necessary files can be updated in time and are available when needed.


    Viewpoint Monitoring


    Viewpoint Monitoring is a powerful application software which can provide the Monitoring, control, trend, alarm and fault data recording function of the substation application. This easy-to-use program can be configured to within a few minutes with full visibility, with the aid of this software, you can also to all GE Multlin device event log and waveform to control, automatic retrieval and archive file.


    Interoperability with the built-in IEC 61850 specification


    IEC 61850 is a new international standard for information exchange and interoperability between intelligent devices in substations. Using B30 compliant with IEC 61850 standard, the protection and control of substation can be reduced cost and simplified engineering design, debugging and maintenance process. During the seven years of implementation of UCA2.0, GE has been leading the way, and now GE is taking the lead in adopting the iec 61850 standard.


    The iec 61850 standard adopts the seamless connection of multi-vendor IED devices. In addition to the interoperability of the devices, these regulations are also designed to control substations through the LAN rather than through the scattered wiring of the RTU. The distributed control of several ieds is implemented in the point-to-point communication mode of the Ethernet network, and this control mode does not require the connection of RTU to the remote SCADA master station. High-speed information transfer saves a lot of expensive hard wire connections.


    Direct I/O communication


    This feature enables a number of UR ieds to exchange binary data through dedicated optical fibers (single or multimode), RS422, G703, or C37.94. Since ieds are directly connected with a ring or redundant (double) ring in this scheme, no switching equipment is needed.


    EnerVistaTM

    EnerVistaTM is an industry-leading software program that simplifies aspects of the B90 application. It becomes a multi-purpose tool for monitoring the bus status in real time and viewing any amount of electrical value measured by B90. EnerVistaTM software is equipped with powerful COMTRADE tools and event sequence viewers that have the ability to analyze any cause of failure. EnerVistaTM software is supplied with B90.


    EnerVistaTMLaunchPad


    The EnerVistaTM LaunchPad is a powerful software package that provides users with all the Settings and support tools needed to configure and maintain all GE Multilin products. The package also includes a file system that ensures that all manuals, application records and other necessary files can be updated in time and are available when needed.


    Viewpoint Monitoring


    Viewpoint Monitoring is a powerful application software which can provide the Monitoring, control, trend, alarm and fault data recording function of the substation application. This easy-to-use program can be configured to within a few minutes with full visibility, with the aid of this software, you can also to all GE Multlin device event log and waveform to control, automatic retrieval and archive file.


    Automated control logic can be easily created and edited using a graphical logic editor


    Viewpoint of Maintenance


    Viewpoint Maintenance is a suite of software tools designed specifically for Maintenance personnel. The software can be used for troubleshooting, maintenance and troubleshooting of the GE Multilin devices that are completed and debugged. Just click on the mouse and the software will provide users with a simplified report that will show any failures or problems with the power system. The use of the software can improve the safety performance of the relay, and it can edit the configuration of the device to form a document and form a report.